MENU > Settings > Refill water
Max. pressure diff.
11319
Circuit
Setting range
Factory setting
1
-5.0 . . . -0.1 bar
-0.5 bar
Setting of the pressure difference below "Max. pressure" to ensure an
acceptable pressure in the heating system.
When the pressure at S10 gets lower than the set difference below "Max.
pressure", the release valve V2 is closed in order to stop reducing the pressure.
See also "Max. pressure"
-5.0 - -0.1:
Set the pressure difference related to "Max.
pressure" at S10.