198
GB
There are 3 terminals for the electrical wiring between the receiver and the hardwired control panel:
• M1: connection of intrusion relays,
• M2: connection of tamper and fault relays and arm/disarm input/output.
• M3: connection of external power supply.
1
Z1
2
Z2
3
Z3
4
Z4
5
Z5
M1
M2
M3
6
Z6
7
Z7
8
Z8
1
TMP
2
FLT
3
RAC
4
5
COM
6
7
ARS
8
GND
1
+VL
2
GND
3
+VL
4
GND
View of terminal blocks
The following table describes the correspondence of different Inputs/Outputs:
(1) Optocoupler output with common contact: max. consumption 100 mA at 30 V DC (resistive load).
(2) Optocoupler output with voltage-free contacts: max. consumption 100 mA at 30 V DC (resistive load).
(3) Input for which parameter can be set and which can be controlled using either a positive or a negative voltage.
3. Installation
3.1 Connections for hardwired inputs/outputs
IMPORTANT: all electrical wiring must be performed with the power off.
IMPORTANT
• Use a shielded cable with a minimum cross-section of 0.22 mm
2
for the receiver signals
and 0.5 mm
2
for the receiver power supply (+VL and GND).
• The maximum length is 100 m if 0.5 mm
2
supply conductors (+VL and GND) are used
and 200 m if 1 mm
2
conductors are used.
Pos.
N°
Name
Description
Type
1
Z1
Zone 1 alarm contact
Output (1)
2
Z2
Zone 2 alarm contact
Output (1)
3
Z3
Zone 3 alarm contact
Output (1)
M1
4
Z4
Zone 4 alarm contact
Output (1)
5
Z5
Zone 5 alarm contact
Output (1)
6
Z6
Zone 6 alarm contact
Output (1)
7
Z7
Zone 7 alarm contact
Output (1)
8
Z8
Zone 8 alarm contact
Output (1))
1
TMP
Tamper alarm contact
Output (1)
2
FLT
System fault status contact
Output (1)
3
RAC
Control device trigger contact
Output (2)
M2
4
RAC
Control device trigger contact
Output (2)
5
COM
Common for output signals
-
6
COM
Common for output signals
-
7
ARS
Control panel connected reference
Input (3)
8
GND
Ground
-
1
+VL
12 V DC external power supply
Input
M3
2
GND
Ground
-
3
+VL
12 V DC external power supply
Input
4
GND
Ground
-