PIM00413
9-6
9.4.2
Digital output
The alarm output single of this unit is a digital signal. Connect these terminals as required, with reference to the
table below.
Terminal
name
Signal name
Output content
:
factory setting
DO1 Digital
output
1
When switching the PQ number, it becomes ON if the pressure
command, flow rate command has reached the goal
DO2 Digital
output
2
No output (Do not connect)
OCOM
Digital output COM
Both positive and negative signals are acceptable
OCOM
DO2
DO1
Load
Load
MAX 50mA
External power
supply
(DC24V)
CAUTION
●
As the external power supply, prepare a 24 VDC ±1 V, 0.5 A power supply. Power cannot be supplied from
this controller to external equipment.
●
The maximum output current of an output circuit is 50mA (resistance load). If you attempt to drive load
higher than the allowable current, the circuit may be damaged. Pay attention to the maximum allowable
current.
●
To drive induction load, take surge preventive measures.
9.4.3
Contact output
The contact output signal for alarms. Connect these terminals as required, with reference to the table below.
Terminal
name
Signal name
Output content
:
factory setting
AL_A
Alarm output a point
Continuity with “Common” exists when the pressure switch is normal.
AL_B
Alarm output b point
Continuity with “Common” exists when the pressure switch works or
alarm occurs.
AL_C
Alarm output common
Common
Alarm output a point
Alarm output b point
Common
AL̲A
AL̲B
電源
ON
:正常時
AL̲C
CAUTION
●
The contact output switching capacity is 30 VDC/0.5 A (resistance load). If you attempt to drive load higher
than the allowable current, the contact may be damaged. Pay attention to the maximum allowable current.
●
The minimum allowable load of the contact output is 10 mVDC/10
μ
A. However, it is an approximate lower
limit that enables the contact to be opened/closed under minute load. This value varies depending on switching
frequency and environmental conditions. We recommend you to check the minimum allowable load in actual
conditions.
●
To drive induction load, take surge preventive measures.
Power ON: normal
Содержание SUT06S3016-30
Страница 2: ......
Страница 12: ......
Страница 20: ...PIM00413 3 6 3 4 Dimensions Motor Pump Type SUT00 SUT00S3016 30...
Страница 21: ...PIM00413 3 7 SUT00S6007 30...
Страница 22: ...PIM00413 3 8 SUT00D4016 30 SUT00D6021 30 Product type Dimension...
Страница 23: ...PIM00413 3 9 Unit Type SUT06 SUT10 SUT06S3016 30...
Страница 24: ...PIM00413 3 10 SUT06S6007 30...
Страница 25: ...PIM00413 3 11 SUT06D4016 30 SUT06D6021 30 1 327 for SUT06D6021 30 2 188 for SUT06D6021 30 2...
Страница 26: ...PIM00413 3 12 SUT10D6021 30...
Страница 36: ......
Страница 38: ......
Страница 42: ......
Страница 54: ......
Страница 64: ......