![Daikin EUWY 24KBZW1 Series Скачать руководство пользователя страница 76](http://html1.mh-extra.com/html/daikin/euwy-24kbzw1-series/euwy-24kbzw1-series_service-manual_3596898076.webp)
Piping Layout
ESIE11-02
1–66
3
11
4
5
Components water
side
The table below describes the main components of the refrigeration circuit on the water side.
11
High-pressure
service port
The high-pressure service port is used to connect a
high-pressure gauge.
12
Liquid receiver
The liquid receiver temporarily holds the refrigerant which has
been liquified by the condensor before being send to the
expansion valve.
13
Accumulator
The accumulator is used to separate the gas from the liquid in
order to prevent the compressor from pumping liquid.
14
4-way valve
The 4-way valve is energized during cooling.
No.
Component
Function / remark
No.
Component
Function / remark
a
Shut-off valve
Makes it possible to shut-off a part of the water
piping for maintenance (e.g. to change a filter).
b
Airport
To purge the water circuit, to prevent air from
entering the water circuit.
c
Service port
The service port is used to connect a pressure
gauge.
d
Water tempera-
ture sensor
The water temperature sensors are used to control
the thermostat function at the heat exchanger inlet.
e
Freeze-up sensor
This protection device shuts down the circuit when
the temperature of the chilled water becomes too
low in order to prevent the water from freezing
during operation.
f
Strainer
This strainer prevents dirt particles from entering
the water circuit.
g
Flow switch
The flow switch is used to check if there is flow.
h
Drain valve
The drain valve is used to drain water from the
circuit.
i
Expansion vessel
The expansion vessel deals with water expansion,
which occurs when the temperature of the water
varies.
j
Pump
The pump circulates the water.
k
Pressure gauge
Standard is the pressure gauge fitted to the unit.
n
Safety valve
Maximum 3 bar pressure.
l
Buffer tank
This buffer tank of 55 l is used to store chilled water
to prevent the compressor from switching ON/OFF
continuously depending on the load.
m
Pressure regula-
tion valve
The pressure regulation valve is used to regulate
the pressure of the water side.
EUWYB5-24KBZW1
EUWYP5-24KBZW1
EUWYN5-
2
4KBZW1
Содержание EUWY 24KBZW1 Series
Страница 2: ......
Страница 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Страница 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Страница 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Страница 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Страница 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Страница 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Страница 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Страница 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Страница 210: ...ESIE11 02 4 Index 3 1 4 5...