Malfunction Indications and Safeties Overview
ESIE11-02
3–12
3
1
3
4
5
Alarm indicators on
I/O PCB
The table below describes the alarm indicators on the I/O PCB.
Alarm indications
on I/O PCB
The table below describes the alarm indications on the I/O PCB.
If more than one alarm is present, the reverse phase has the highest priority.
Service information
for alarm
indications
■
If the error is solved, H1P and H2P keep their latest status. They can only be reset by switching
OFF/ON the power from the I/O PCB.
■
If alarm codes
fl
and
hp1
are flashing alternately, the alarm is likely to be caused by the reverse
phase protection or by the fuse for evaporator heater tape (F4) that was blown.
Symbol
Indication
HAP
Green LED
■
Blinking = CPU OK
■
Not blinking = CPU NOK
H1P
Red LED
H2P
Red LED
Indication
H1P
H2P
No error
OFF
OFF
Safety device
ON
OFF
Reverse phase
OFF
ON
Sensor defective
ON
ON
Содержание EUWY 24KBZW1 Series
Страница 2: ......
Страница 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Страница 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Страница 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Страница 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Страница 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Страница 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Страница 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Страница 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Страница 210: ...ESIE11 02 4 Index 3 1 4 5...