An overview of the malfunction indications and safeties is given in "Malfunction Indications and
Safeties Overview" on page 3–7.
Flow switch or
pump contact
■
Damaged flow switch
■
Incorrect pump operation
■
Incorrect field wiring
■
Defective control devices
(pump relay)
■
Flow switch
■
Pump operation
■
Field wiring
■
Control devices
Discharge ther-
mal protector
■
Refrigerant shortage
■
Operation out of range
■
Refrigerant leak
■
Operation condition
Fan thermal
protector
■
Blocked fan
■
Blocked condenser
■
State of the fans (free rotation)
■
State of the condenser
Reverse phase
protection
■
Incorrect phase direction
■
One phase missing
■
Swap two phases
■
Connect the loose phase
Malfunction
Possible causes
Items to be checked