General Outline
ESIE11-02
1–22
3
11
4
5
(2)
: The sound power level is an absolute value that does not depend on the surroundings or the
distance. It cannot be measured in the field (ISO 9614).
Nominal conditions
The nominal conditions are as follows:
■
Entering/leaving evaporator water temperature 12.5/7°C
■
Ambient air temperature 35°C
■
Power input is total input: Comp control c fans + pump.
Operation range
The nominal operation range covers:
■
A leaving evaporator water temperature from 5°C (-5°C/-20°C for ZH/ZL option) to 20°C (pull down
condition to 25°C).
■
A leaving condensor water temperature from 35°C to 50°C.