Inputs and Outputs Overview
ESIE11-02
3–4
3
1
3
4
5
1.2
Inputs and Outputs Overview: EUWA*5-24KBZW1 and EUWY*5-24KBZW1
Inputs/outputs
The table below describes the relation between the wiring diagram symbols, the wiring connections
and the error codes.
For the exact location, see:
■
"PCB Layout of the EUWA*5-24KBZW1 and EUWY*5-24KBZW1" on page 1–71.
■
"Wiring Diagram: EUWA*5-24KBZW1 and EUWY*5-24KBZW1" on page 1–75.
Type
Device
Wiring
diagram
symbol
Wiring con-
nection
terminal
Error code
Description
Analog
input
Sensor
R3T
X1/B1-GND
e1
Inlet water temperature sensor
R4T
X1/B2-GND
e2
Outlet water temperature sensor
Digital input
Trans-
ducer
K4S + S1HP
+ QID
K5S + S2HP
+ Q2D
X1/ID3-GND
hp1
Overcurrent relay + high pressure
discharge protector
S4LP/S5LP
X1/ID4-GND
lp1
Low-pressure switch
Control
contacts
S9S (field)
X1/ID5-GND
(
h7
)
Switch for remote start/stop or dual setpoint
S7S (field)
X1/ID2-GND
(
h6
)
Switch for remote cool/heat selection or
dual setpoint
S10L
X1/ID1-GND
(
fl
)
Flow switch
Digital out-
put
—
K1M
X2C1/2-NO1
—
Compressor 1 contactor
K2M
X2C1/2-NO2
—
Compressor 2 contactor
K1P (field)
X2C3/4-NO3
—
Pump contactor
Y1R/Y2R
X2C3/4-NO3
—
Reversing valve
H1P (field)
X2C5-NO5
—
Indication lamp alarm
Содержание EUWY 24KBZW1 Series
Страница 2: ......
Страница 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Страница 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Страница 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Страница 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Страница 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Страница 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Страница 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Страница 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Страница 210: ...ESIE11 02 4 Index 3 1 4 5...