![Daikin EUWY 24KBZW1 Series Скачать руководство пользователя страница 157](http://html1.mh-extra.com/html/daikin/euwy-24kbzw1-series/euwy-24kbzw1-series_service-manual_3596898157.webp)
ESIE11-02
Troubleshooting
3–29
3
3
4
5
1
Modify parameters
according to
required unit model
The factory menu is used to set up the identification parameters according to the required unit model.
Most of the settings are already preset (also for spare part controller). The table below gives the
parameter code and the value of the parameters that have to be modified according to the unit model.
(*) Bold = different from default, “-” = not applicable because of other setting
Additionally confirm correct default settings of following parameters:
■
P8 should be equal to 1
■
P9 should be equal to 9
To exit the factory
menu
To exit the factory menu when you have changed all parameters, proceed as follows:
Parameter code
D
escript
ion
D
efau
lt valu
e (S-
P
)
U
n
it of
m
easu
re
m
ent
EUW
A*5-8
-10-
12K* st
and
ar
d
EUW
A
*5-8
-10-
12K* OP
Z
L
EUW
A
*5-8
-10-
12K* OP
Z
H
EUW
A
*16-
20-24K
* s
tan
dard
EUW
A
*16-
20-24K
* OP Z
L
EUW
A
*16-
20-24K
* OP Z
H
(/*)
/03
Probe type B3
1
-
1
1
1
1
1
1
(A*)
A01
Anti-freeze alarm
setpoint
4
°C
4
-11,5
-6,5
4
-11,5
-6,5
A02
Anti-freeze alarm
hysteresis
3,5
°C
3,5
3,5
3,5
3,5
3,5
3,5
A04
Anti-freeze heater
setpoint
4
°C
4
-10
-5
4
-10
-5
H*
H01
Unit type
2
-
2
2
2
2
2
2
H04
Number of comp/unit
0
-
0
0
0
1
1
1
H11
Output modes
0
-
0
0
0
9
9
9
(r*)
r13
Min. cooling setpoint
7
°C
7
-7
-2
7
-7
-2
r14
Max. cooling setpoint
25
°C
25
25
25
25
25
25
Step
Action
1
Press
p
.
2
Turn OFF the power supply.
Содержание EUWY 24KBZW1 Series
Страница 2: ......
Страница 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Страница 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Страница 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Страница 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Страница 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Страница 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Страница 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Страница 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Страница 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Страница 210: ...ESIE11 02 4 Index 3 1 4 5...