Main Functions
Si18-201
88
Main Functions
1.1.16
Automatic Operation (Heat Pump Only)
Automatic Cooling/Heating Function
When the AUTO mode is selected with the remote controller, the microcomputer automatically
determines the operation mode from cooling and heating according to the room temperature
and setting temperature at the time of the operation startup, and automatically operates in that
mode.
The unit automatically switches the operation mode to cooling or heating to maintain the room
temperature at the main unit setting temperature.
Detailed
explanation of the
function
1. Remote controller setting temperature is set as automatic cooling / heating setting
temperature (18 to 30°C).
2. Main unit setting temperature equals remote controller setting temperature plus correction
value (correction value / cooling: 0 deg, heating: 2 deg.).
3. Operation ON / OFF point and mode switching point are as follows.
Heating
→
Cooling switching point: Room temperature
≥
Main unit setting temperature
+2.5 deg.
Cooling
→
Heating switching point: Room temperature < Main unit setting temperature –
2.5 deg.
Thermostat ON / OFF point is the same as the ON / OFF point of cooling or heating
operation.
4. During initial operation
Room temperature
≥
Remote controller setting temperature: Cooling operation
Room temperature < Remote controller setting temperature: Heating operation
However, in the automatic Powerful cooling/heating mode, the guard timer is set as follows to
prevent hunting in cooling / heating mode.
0.5 C
LHz
LHz
LHz
*
55Hz
*
55Hz
LHz indicates low frequency. Item marked with varies depending on models.
ON point
Frequency switching
point
OFF point
5 min
5 min
Compressor
control
Stop
Stop
Stop
Stop
Stop
Stop
Indoor unit fan
Extra-low air flow
Extra-low air flow
Low air flow
Low air flow
(ML047)
Heating /
cooling switching point
2.5 deg.
or higher
(Heating thermostat
OFF point)
Main unit setting
temperature
(Cooling thermostat
OFF point)
Cooling /
heating switching point
Cooling
operation
Heating
operation
Cooling
operation
With compressor capacity supplied
With no compressor capacity supplied
(1.5 deg.)
or higher
Less than
(1.5 deg.)
2.5 deg.
or higher
(RL022)
Содержание BPMK928B42
Страница 9: ...Si18 201 viii Table of Contents ...
Страница 71: ...Specifications Si18 201 58 Specifications ...
Страница 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ ...
Страница 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ ...
Страница 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H ...
Страница 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J ...
Страница 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC ...
Страница 214: ...Si18 201 Remote Controller Operations 201 ...
Страница 216: ...Si18 201 Remote Controller Operations 203 ...
Страница 217: ...Remote Controller Si18 201 204 Operations ...
Страница 234: ...Si18 201 Method of Field Set Operating Test 221 2 3 Interface Adaptor for Room Airconditioner KRP928A1S ...
Страница 237: ...Method of Field Set Si18 201 224 Operating Test ...
Страница 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249 ...
Страница 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C ...
Страница 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9 ...
Страница 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION ...
Страница 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C ...