Troubleshooting - Outdoor Unit Related
Si18-201
260
Service Diagnosis
3. Troubleshooting - Outdoor Unit Related
3.1
The Unit Runs but Doesn’t Cool (Heat) the Room
Supposed
Causes
"
Incorrect temperature setting
"
Unconnectable models
"
Clogged air filter
"
Improper load for the capacity
"
Excessively long refrigerant pipe
"
Faulty installation of indoor unit / outdoor unit
"
Clogged refrigerant circuit, etc.
"
Gas shortage
"
Stop valve closed
"
EVn malfunction
"
EVH malfunction
"
EVP malfunction
Troubleshooting
Check No.1
Refer to P.300
Check No.9
Refer to P.306
YES
Set the temperature at the
desired again.
Connect the correct types
of units.
Clean.
Replace by suitable model
or install additional unit.
Make it within the specified
length.
Refer to the contents of
Checking installation
status.
Refer to the contents of
Refrigerant system check
Perform the same remedy
as that when lack of gas is
detected.
Is the
temperature set
correctly?
Are the
types of indoor and
outdoor units correctly
selected to
connect?
YES
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
NO
While thermostat is OFF.
Check through the
compatibility table
NO
Is the air filter clogged?
YES
YES
Is the load suitable
for the capacity?
NO
NO
Is the
refrigerant piping too
long?
YES
Are the
indoor and outdoor
units installed
normally?
NO
Check No.1
installation condition check.
NO
Check No.9
Refrigerant system
check
There is some faulty point.
YES
Normal
Does gas leak?
NO
To next page
1
Check gas for leaking.
YES
(MF018)
Содержание BPMK928B42
Страница 9: ...Si18 201 viii Table of Contents ...
Страница 71: ...Specifications Si18 201 58 Specifications ...
Страница 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ ...
Страница 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ ...
Страница 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H ...
Страница 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J ...
Страница 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC ...
Страница 214: ...Si18 201 Remote Controller Operations 201 ...
Страница 216: ...Si18 201 Remote Controller Operations 203 ...
Страница 217: ...Remote Controller Si18 201 204 Operations ...
Страница 234: ...Si18 201 Method of Field Set Operating Test 221 2 3 Interface Adaptor for Room Airconditioner KRP928A1S ...
Страница 237: ...Method of Field Set Si18 201 224 Operating Test ...
Страница 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249 ...
Страница 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C ...
Страница 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9 ...
Страница 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION ...
Страница 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C ...