System control
Si18-201
146
Main Functions
3.26.2 Outdoor Unit Motorized Valve Opening Restriction
Outline
This function restricts the opening degree of the outdoor unit motorized valves (discharge
bypass motorized valve, gas pipe motorized valve and liquid pipe motorized valve) in order to
quickly stabilize and control the system.
1. EVP opening restriction
There are two types of EVP control: complete closing and completely closing with retightening
EVP's max. opening is set to EVPMAX.
EVP's min. opening is set to EVPMIN.
The motorized valve operates as follows when it is fully closed and at min. opening.
When EVP closes from open condition ("EVP open condition"), EVPMIN is set as the lower
limit. When it closes from EVPMIN, the next motorized valve opening degree is set to 0
pulse ("fully closed condition").
EVP is in the "fully closed condition" from 0 pulse to EVPDP pulses, and the opening degree
increments. In the fully closed condition, EVPDP pulses is set as the upper limit. When it
opens from the EVPDP condition, the next valve opening degree is set to EVPDP
to achieve "EVP open condition."
2. EVG (gas pipe motorized valve) opening restriction
"
Not in capacity control during normal heating
operation
"
ELV fully closed during normal cooling operation
(after TEVGARD elapsed 30 sec or more)
"
In capacity control during normal heating
operation
"
EVL not fully closed during normal cooling
operation
EVPMAX:
Cooling 250 pulses
Heating 450 pulses
10
EVPMIN: 32 pulses
Closed condition
(M1055)
0
Outdoor unit valve opening restriction
EVP (discharge bypass motorized valve)
EVGMAX: 70 pulses
(10)
EVGMIN: 12 pulses
0 pulse
Closed condition
(M1038)
EVGMAX: 100 pulses
EVGMIN: 12 pulses
0 pulse
(M1039)
EVGMAX: 150 pulses
GDP10
EVGMIN: 12 pulses
Closed condition
(M1040)
EVGMAXC: 450 pulses
GDP10
EVGMIN: 12 pulses
Closed condition
(M1041)
Содержание BPMK928B42
Страница 9: ...Si18 201 viii Table of Contents ...
Страница 71: ...Specifications Si18 201 58 Specifications ...
Страница 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ ...
Страница 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ ...
Страница 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H ...
Страница 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J ...
Страница 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC ...
Страница 214: ...Si18 201 Remote Controller Operations 201 ...
Страница 216: ...Si18 201 Remote Controller Operations 203 ...
Страница 217: ...Remote Controller Si18 201 204 Operations ...
Страница 234: ...Si18 201 Method of Field Set Operating Test 221 2 3 Interface Adaptor for Room Airconditioner KRP928A1S ...
Страница 237: ...Method of Field Set Si18 201 224 Operating Test ...
Страница 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249 ...
Страница 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C ...
Страница 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9 ...
Страница 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION ...
Страница 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C ...