Si18-201
Troubleshooting - SkyAir Indoor Unit
Service Diagnosis
257
2.6.5
Failure of Capacity Setting
Remote
Controller
Display
AJ
Applicable
Models
FHYC
Method of
Malfunction
Detection
Capacity is determined according to resistance of the capacity setting adaptor and the memory
inside the IC memory on the indoor unit PC board, and whether the value is normal or abnormal
is determined.
Malfunction
Decision
Conditions
Operation and:
(1)When the capacity code is not contained in the PC board’s memory, and the capacity setting
adaptor is not connected.
(2)When a capacity that doesn’t exist for that unit is set.
Supposed
Causes
"
Failure of capacity setting adaptor connection
"
Failure of indoor unit PC board
Troubleshooting
Note:
Capacity is factory set in the data IC on the PC board. A capacity setting adaptor that matches
the capacity of the unit is required in the following case.
If the indoor PC board installed at the factory is for some reason changed at the installation site,
the capacity will not be contained in the replacement PC board.
If you connect a capacity setting adaptor to a PC board in which the capacity is memorized, the
capacity setting for the PC board will become the capacity setting of the adaptor. (Priority of
capacity setting adaptor)
Turn the power supply off
once and back on.
Is the
capacity setting
adaptor plugged into X23A
of the indoor unit PC
board?
NO
Is AJ displayed on
the remote controller?
NO
YES
YES
Plug a capacitor setting
adaptor that matches the
capacity of the unit into X23A.
(See note)
Indoor unit PC board
replacement
Could be outside cause (noise,
etc.) other than malfunction.
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(MF015)
Содержание BPMK928B42
Страница 9: ...Si18 201 viii Table of Contents ...
Страница 71: ...Specifications Si18 201 58 Specifications ...
Страница 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ ...
Страница 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ ...
Страница 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H ...
Страница 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J ...
Страница 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC ...
Страница 214: ...Si18 201 Remote Controller Operations 201 ...
Страница 216: ...Si18 201 Remote Controller Operations 203 ...
Страница 217: ...Remote Controller Si18 201 204 Operations ...
Страница 234: ...Si18 201 Method of Field Set Operating Test 221 2 3 Interface Adaptor for Room Airconditioner KRP928A1S ...
Страница 237: ...Method of Field Set Si18 201 224 Operating Test ...
Страница 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249 ...
Страница 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C ...
Страница 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9 ...
Страница 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION ...
Страница 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C ...