Si18-201
Troubleshooting - Outdoor Unit Related
Service Diagnosis
271
3.3.9
Operation Halt Due to Faulty Position Detection Sensor
Outdoor Unit
Indication
H6
Method of
Malfunction
Detection
Faulty start of the compressor is detected by checking the turning information of the compressor
via position detector of electrical parts.
Malfunction
Decision
Conditions
When the compressor did not turn in approximately 15 seconds after starting operation.
Frequency: 4 times
Clear condition: 60-minute continuous run (normal)
Supposed
Causes
"
Incorrect detection due to disconnected relay of compressor
"
Malfunction to start due to faulty compressor
"
Malfunction to start due to faulty outdoor unit PC board
"
Malfunction to start due to stop valve "closed"
"
Incorrect detection due to faulty outdoor unit PC board
"
Input voltage error
Troubleshooting
Check No.6
Refer to P.303
Check No.7
Refer to P.304
YES
Correct the connection.
Replace electrical parts.
Correct the connection.
Replace outdoor PC board.
Check harness.
Replace outdoor unit PC
board.
Replace compressor.
(MF028)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is it 300-350V?
NO
YES
Is harness
of electrical parts or
compressor correctly
connected?
YES
Is harness of
electrical parts correctly
connected?
Is it normal?
NO
Do respective
phases, U,V,W, output in
good balance?
Check No. 6
Capacitor voltage check
NO
NO
Check No. 6
Power transistor check
YES
Check No. 7
Power transistor output check
NO
YES
Содержание BPMK928B42
Страница 9: ...Si18 201 viii Table of Contents ...
Страница 71: ...Specifications Si18 201 58 Specifications ...
Страница 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ ...
Страница 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ ...
Страница 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H ...
Страница 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J ...
Страница 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC ...
Страница 214: ...Si18 201 Remote Controller Operations 201 ...
Страница 216: ...Si18 201 Remote Controller Operations 203 ...
Страница 217: ...Remote Controller Si18 201 204 Operations ...
Страница 234: ...Si18 201 Method of Field Set Operating Test 221 2 3 Interface Adaptor for Room Airconditioner KRP928A1S ...
Страница 237: ...Method of Field Set Si18 201 224 Operating Test ...
Страница 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249 ...
Страница 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C ...
Страница 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9 ...
Страница 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION ...
Страница 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C ...