Si18-201
Troubleshooting - Outdoor Unit Related
Service Diagnosis
301
3.4.3
Electronic Expansion Valve Check
Check No.3
Conduct the followings to check the electronic expansion valve (EV).
1. Check to see if the EV connector is correctly inserted in the PCB. Compare the EV unit and
the connector number.
2. Turn the power off and back on again, and check to see if all the EVs generate latching
sound.
3. If any of the EVs does not generate latching noise in the above step 2, disconnect that
connector and check the conductivity using a tester.
Check the conductivity between pins 1, 3 and 6, and between pins 2, 4 and 5. If there is no
conductivity between the pins, the EV coil is faulty.
4. If no EV generates latching sound in the above step 2, the outdoor unit PCB is faulty.
5. If the conductivity is confirmed in the above step 2, mount a good coil (which generated
latching sound) in the EV unit that did not generate latching sound, and check to see if that
EV generates latching sound.
∗
If latching sound is generated, the outdoor unit PCB is faulty.
∗
If latching sound is not generated, the EV unit is faulty.
Note:
Please note that the latching sound varies depending on the valve type.
3.4.4
Fan Motor Position Signal Check
Check No.4
Measurement method
1. Turn the power supply on.
2. Check the voltage of U-,V-,W-Phase of the above upper and lower fans with fan rotating.
3. The waveform measured will be as shown below.
4. It is OK if , as shown above 3, approximately 5V voltage is turned on and off.
6P Connector
1 2 3 4 5 6
5P Connector
1 2 3 4 5
Harness 6P
Harness 5P
Check
5 – 2
5 – 4
6 – 1
6 – 3
Check
5 – 1
5 – 2
5 – 3
5 – 4
Locations for measurement
(Upper/Lower fans + U-,V-,W-
Phase)
Multiple-meter, + side (A)
- side (B)
S514
S504
S501
S506
Q504
U
Q503
V
Q502
W
Q507
U
Q506
V
Q505
W
PCB2
GND
(Q0003)
(B)
(A)
(A)
(A)
(A)
(A)
(A)
+5V
(Q0004)
Содержание BPMK928B42
Страница 9: ...Si18 201 viii Table of Contents ...
Страница 71: ...Specifications Si18 201 58 Specifications ...
Страница 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ ...
Страница 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ ...
Страница 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H ...
Страница 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J ...
Страница 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC ...
Страница 214: ...Si18 201 Remote Controller Operations 201 ...
Страница 216: ...Si18 201 Remote Controller Operations 203 ...
Страница 217: ...Remote Controller Si18 201 204 Operations ...
Страница 234: ...Si18 201 Method of Field Set Operating Test 221 2 3 Interface Adaptor for Room Airconditioner KRP928A1S ...
Страница 237: ...Method of Field Set Si18 201 224 Operating Test ...
Страница 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249 ...
Страница 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C ...
Страница 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9 ...
Страница 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION ...
Страница 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C ...