System control
Si18-201
120
Main Functions
3.7
Oil Return Operation
Purpose of the
Function
To collect refrigerating machine oil that adheres on the internal connection pipe wall during
regular operation and send it to the compressor.
Outline
The oil recovery operation is conducted in the cooling cycle in both heating and cooling modes.
The oil recovery operation collects oil dissolved in liquid refrigerant from High Hz and Low Hz
(two types in both cooling and heating) and the section between Refnet joint and branch unit if
there is a non-operating branch unit during cooling operation.
Oil recovery function in cooling operation
The opening of bypass motorized valve in branch unit shall be 450 pulses during oil recovery
operation.
Oil recovery function in heating operation
Similar to the reverse cycle defrost, oil is collected by the cooling cycle.
The opening of bypass motorized valve in branch unit shall be 100 pulses during oil recovery
operation.
The oil recovery interval setting timer is set to 3 hours.
Details
Oil recovery operation in cooling mode
In cooling operation, two types of oil recovery operations are conducted. One type of operation
collects refrigerating machine oil adhered on the main pipe wall and sends it to the compressor.
The other type, called non-operating BP oil recovery operation, collects refrigerating machine oil
seeping into non-cooling room units.
The intervals of operations to recover oil from the main pipe become shorter when the operating
frequency exceeds the specified frequency.
Main pipe oil recovery operation
When the operating frequency exceeds 75 Hz even once after an oil recovery operation, the oil
recovery operation interval becomes 5 hours. When the operating frequency does not exceed
75 Hz, the operation interval is 8 hours.
The minimum time of main pipe oil recovery operation time is 2 minutes. The maximum time is
5 minutes when High Hz appears. Under normal Hz, the operation time is 5 minutes.
During a main pipe oil recovery operation, the opening of the EVHs of BP units are set to 450
pulses when High Hz appears, but under normal Hz the opening are set to 450 pulses.
Non-operating BP oil recovery operation
When a BP unit with non-operating room units remain in that condition for 90 minutes while
room units of other BP units are operating, an oil recovery operation is activated to collect oil
from non-operating room units.
The opening of the EVHs of BPs for which the non-operating BP oil recovery operation is
conducted are set to 450 pulses.
The opening of the EVHs of BPs for which the non-operating room unit oil recovery operation is
conducted are set to 450 pulses.
The minimum and maximum times of non-operating BP oil recovery operation are 2 minutes
and 5 minutes, respectively.
Integral Timer
Oil Recovery Time
Oil recovery from non-operating
branch unit
TRAC1
1.5 hours
TRBC1
2 minutes
Oil recovery during High Hz appearing
TRAC2
5 hours
TRBC2
2 minutes
Oil recovery during Low Hz operation
TRAC3
8 hours
TRBC3
2 minutes
Содержание BPMK928B42
Страница 9: ...Si18 201 viii Table of Contents ...
Страница 71: ...Specifications Si18 201 58 Specifications ...
Страница 206: ...Si18 201 Remote Controller Operations 193 1 1 2 FVX25 35KZ ...
Страница 207: ...Remote Controller Si18 201 194 Operations 1 1 3 FTXD25 35KZ ...
Страница 208: ...Si18 201 Remote Controller Operations 195 1 1 4 FTK FTX50 60H ...
Страница 209: ...Remote Controller Si18 201 196 Operations 1 1 5 FTKD FTXD50 60 71J ...
Страница 213: ...Remote Controller Si18 201 200 Operations 1 1 9 FHYC35 50 60 71K Optional Accessory BRC7C612WC ...
Страница 214: ...Si18 201 Remote Controller Operations 201 ...
Страница 216: ...Si18 201 Remote Controller Operations 203 ...
Страница 217: ...Remote Controller Si18 201 204 Operations ...
Страница 234: ...Si18 201 Method of Field Set Operating Test 221 2 3 Interface Adaptor for Room Airconditioner KRP928A1S ...
Страница 237: ...Method of Field Set Si18 201 224 Operating Test ...
Страница 262: ...Si18 201 Troubleshooting SkyAir Indoor Unit Service Diagnosis 249 ...
Страница 393: ...Wiring Diagrams Si18 201 380 Appendix FHYC35 50 60 71KVE9 3D005668C ...
Страница 394: ...Si18 201 Wiring Diagrams Appendix 381 FHYC35 50 60 71KV1C9 ...
Страница 395: ...Wiring Diagrams Si18 201 382 Appendix FDYM60 03FAV1 FDYM60 03FAVAL C 3D019816D OPTION ...
Страница 396: ...Si18 201 Wiring Diagrams Appendix 383 FDYM60 03FAV1C ...