10
|
Commissioning
Installer reference guide
185
EHYH EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
There is NO
water leak
inside the indoor unit.
There is NO
water leak
inside the gas boiler.
There is NO
water leak
in the connection between the gas boiler and the indoor unit.
The
shut-off valves
are properly installed and fully open (field supply).
The
stop valves
(gas and liquid) on the outdoor unit are fully open.
The
air purge
valve is open (at least 2 turns).
The
pressure relief valve
purges water when opened. Clean water must come out.
The
gas boiler
is switched ON.
Setting . is correctly set on the gas boiler.
▪
0=for EH EHYHBH08
▪
1=for EHYHBX08
The
minimum water volume
is guaranteed in all conditions. See "To check the water
volume and flow rate" in
44].
10.4 Checklist during commissioning
The
minimum flow rate
is guaranteed in all conditions. See "To check the water volume
44].
To perform an
air purge
.
To perform a
test run
.
To perform an
actuator test run
.
Underfloor screed dryout function
The underfloor screed dryout function is started (if necessary).
To perform a gas pressure test.
To perform a test run on the
gas boiler
.
10.4.1 To check the minimum flow rate
1
Confirm according to the hydraulic configuration which space heating loops
can be closed due to mechanical, electronic, or other valves.
2
Close all space heating loops that can be closed (see previous step).
3
Start the pump test run operation (see
"10.4.4 To perform an actuator test
189]).
4
Go to [6.1.8]: >
Information
>
Sensor information
>
Flow rate
to
check the flow rate. During pump test run operation, the unit can operate
below this minimum required flow rate.