8
|
Configuration
Installer reference guide
131
EHYH EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
d
Shower (field supply)
e
Inlet on boiler
f
Recirculation thermistor (EKTH2) (field supply)
g
Water supply
h
Non-return valve (field supply)
In case of [E‑06]=1
Domestic hot water pump installed for…
Instant hot water
Disinfection
c
f
b
a
g
c
b
a
d f
e g
a
Indoor unit
b
Tank
c
Domestic hot water pump (field supply)
d
Heater element (field supply)
e
Non‑return valve (field supply)
f
Shower (field supply)
g
Cold water
INFORMATION
The correct domestic hot water default settings become only applicable when
domestic hot water operation is activated ([E‑05]=1).
Thermostats and external sensors
#
Code
Description
[A.2.2.4]
[C-05]
Contact type main
In external room thermostat control, the contact
type of the optional room thermostat or heat
pump convector for the main leaving water
temperature zone must be set.
▪
1 (
Thermo ON/OFF
): The connected external
room thermostat or heat pump convector
sends the heating or cooling demand by the
same signal as it is connected to only 1 digital
input (preserved for the main leaving water
temperature zone) on the indoor unit (X2M/1).
Select this value in case of a connection to the
heat pump convector (FWXV).
▪
2 (
H/C request
)(default): The connected
external room thermostat sends separate
heating and cooling demand and is therefore
connected to the 2 digital input (preserved for
the main leaving water temperature zone) on
the indoor unit (X2M/1 and 2). Select this value
in case of connection with the wired (EKRTWA)
or wireless (EKRTR1) room thermostat.