6
|
Preparation
Installer reference guide
55
EHYH EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
Item
Description
Wires
Maximum
running current
Optional equipment
7
3‑way valve
3
100 mA
(b)
8
Domestic hot water tank
thermistor
2
(d)
9
Power supply for drain pan
heater
2
(b)
10
Room thermostat/heat
pump convector
3 or 4
100 mA
(b)
11
Outdoor ambient
temperature sensor
2
(b)
12
Indoor ambient
temperature sensor
2
(b)
Field supplied components
13
Shut-off valve
2
100 mA
(b)
14
Electricity meter
2
(b)
15
Domestic hot water pump
2
(b)
16
Alarm output
2
(b)
17
Changeover to external heat
source control
2
(b)
18
Space cool/heat operation
control
2
(b)
19
Power consumption digital
inputs
2 (per input signal)
(b)
20
Gas meter
2
(b)
21
Safety thermostat
2
(e)
(a) Refer to name plate on outdoor unit.
(b) Minimum cable section 0.75 mm².
(c) Use the cable supplied with the boiler.
(d) The thermistor and connection wire (12 m) are delivered with the domestic hot
water tank.
(e) Cable section 0.75 mm² till 1.25 mm²; maximum length: 50 m. Voltage-free contact
shall ensure the minimum applicable load of 15 V DC, 10 mA.
(f) Cable section 0.75 mm² till 1.25 mm²; maximum length: 500 m. Applicable for both
single user interface and dual user interface connection.
(g) Cable section 1.5 mm
2
; maximum length: 50 m.
NOTICE
More technical specifications of the different connections are indicated on the inside
of the indoor unit.