The horizontal flue MUST be installed under a 3° fall towards the boiler (50 mm per
metre) and MUST be supported with a minimum of 1 bracket at each meter length.
Best recommended position of the bracket is just before the joint.
INFORMATION
Flexible flue gas lines may NOT be used in horizontal connection sections.
INFORMATION
The maximum lengths in the table below apply to each gas boiler separately.
C
83
(6)
C
43
(5)
Twin-80
60/100
80/125
Twin-80
L1+L2 (m)
L1 (m)
L1 (m)
L1+L2 (m)
80
10
29
80
Special remark regarding
C
83
:
See the table below for the minimum diameters of
the combined gas exhaust system.
Number of units
Minimum Ø
2
130
3
150
4
180
5
200
6
220
7
230
8
250
9
270
10
280
11
290
12
300