8
|
Configuration
Installer reference guide
179
EHYH EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
Measured value at maximum
power
Adjustment values CO
2
(%) at minimum power
(front cover opened)
Natural gas 2H (G20,
20 mbar)
Propane 3P (G31,
30/50/37 mbar)
10.8
—
10.5±0.1
10.6
10.3±0.1
10.4
10.1±0.1
10.2
9.9±0.1
10.0
9.8±0.1
9.8
9.6±0.1
9.6
9.0±0.1
—
9.4
8.9±0.1
9.2
8.8±0.1
9.0
8.7±0.1
8.8
8.6±0.1
8.6
8.5±0.1
3
After measuring the CO
2
percentage and adjusting the setting, put the cover
cap and the sampling point back in their place. Make sure they are gastight.
4
Select High setting by simultaneously pressing and twice. Capital will
appear on the service display.
5
Measure the CO
2
percentage. If the CO
2
percentage still deviates from the
values in the table indicating the CO
2
percentage at maximum power, contact
your local dealer.
6
Press and simultaneously to exit the test program.
7
Put the front panel back in its place.