13
|
Troubleshooting
Installer reference guide
207
EHYH EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
Possible causes
Corrective action
The water volume in the installation is
too high
Make sure that the water volume in the
installation is below the maximum
allowed value (see
"6.4.4 Changing the pre-pressure of the
expansion vessel"
50]).
The water circuit head is too high
The water circuit head is the difference
in height between the indoor unit and
the highest point of the water circuit. If
the indoor unit is located at the highest
point of the installation, the installation
height is considered 0 m. The maximum
water circuit head is 7 m.
Check the installation requirements.
13.3.5 Symptom: The water pressure relief valve leaks
Possible causes
Corrective action
Dirt is blocking the water pressure relief
valve outlet
Check whether the pressure relief valve
works correctly by turning the red knob
on the valve counterclockwise:
▪
If you do NOT hear a clacking sound,
contact your dealer.
▪
If the water keeps running out of the
unit, close both the water inlet and
outlet shut-off valves first and then
contact your dealer.
13.3.6 Symptom: The space is NOT sufficiently heated at low outdoor temperatures
Possible causes
Corrective action
Gas boiler operation is not activated
Check and make sure that:
▪
The gas boiler is switched On and is
NOT in standby mode.
▪
The communication cable between
the gas boiler and the indoor unit is
properly mounted.
▪
There is no error code on the gas
boiler display.
The gas boiler equilibrium temperature
has not been configured correctly
Increase the "equilibrium temperature"
to activate gas boiler operation at a
higher outdoor temperature. Go to:
▪
[A.5.2.2] >
Installer settings
>
Heat
sources
>
Boiler
>
Equilibrium temp.
OR
▪
[A.8] >
Installer settings
>
Overview settings
[5‑01]