8
|
Configuration
Installer reference guide
160
EHYH EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
#
Code
Description
N/A
[5-04]
Setpoint correction for domestic hot water
temperature.
Setpoint correction for the domestic hot water
temperature, to be applied at low outdoor
temperature when space heating priority is
enabled. The corrected (higher) setpoint will
make sure that the total heat capacity of the
water in the tank remains approximately
unchanged, by compensating for the colder
bottom water layer of the tank (because the
heat exchanger coil is not operational) with a
warmer top layer.
Range: 0°C~20°C
Auto-restart
When power returns after a power supply failure, the auto restart function
reapplies the remote controller settings at the time of the power failure.
Therefore, it is recommended to always enable the function.
If the preferential kWh rate power supply is of the type that power supply is
interrupted, always enable the auto restart function. Continuous indoor unit
control can be guaranteed independent of the preferential kWh rate power supply
status, by connecting the indoor unit to a normal kWh rate power supply.
#
Code
Description
[A.6.1]
[3‑00]
Is the auto restart function of the unit allowed?
▪
0:
No
▪
1 (default):
Yes
Preferential kWh rate power supply
INFORMATION
The preferential kWh rate power supply contact is connected to the same terminals
(X5M/3+4) as the safety thermostat. It is only possible for the system to have EITHER
preferential kWh rate power supply OR a safety thermostat.