weather-dependent operation is active, the water temperature is determined
automatically depending on the outdoor temperature. Low outdoor temperatures
will result in warmer water and vice versa. During weather-dependent operation,
the user has the possibility to shift up or down the target water temperature by a
maximum of 10°C.
See the user reference guide and/or operation manual for more details about this
function.
Leaving water temperature: Main zone
#
Code
Description
[A.3.1.1.1]
N/A
LWT setpoint mode
:
▪
Fixed
:
The
desired
leaving
water
temperature is:
-
NOT weather-dependent (i.e. does NOT
depend
on
the
outdoor
ambient
temperature)
-
fixed in time (i.e., NOT scheduled)
▪
Weather dep.
(default): The desired leaving
water temperature is:
-
weather-dependent (i.e. depends on the
outdoor ambient temperature)
-
fixed in time (i.e., NOT scheduled)
continued >>
#
Code
Description
[A.3.1.1.1]
N/A
<< continuation
▪
Fixed/scheduled
: The desired leaving
water temperature is:
-
NOT weather-dependent (i.e., does NOT
depend
on
the
outdoor
ambient
temperature)
-
according a schedule. The scheduled
actions consists of desired shift actions,
either preset or custom.
Remark:
This value can only be set in
leaving water temperature control.
▪
WD/scheduled
: The desired leaving water
temperature is:
-
weather-dependent (i.e., does depend on
the outdoor ambient temperature)
-
according a schedule. The scheduled
actions consists of desired leaving water
temperatures either preset or custom
Remark:
This value can only be set in
leaving water temperature control.