8
|
Configuration
Installer reference guide
140
EHYH EHYHBH/X08AF + EHYKOMB33AA
Daikin Altherma hybrid heat pump
4P355634-1F – 2020.10
#
Code
Description
[7.7.2.2]
[0‑04]
[0‑05]
[0‑06]
[0‑07]
<< continuation
▪
[0‑07]: Low outdoor ambient temperature.
10°C~25°C (default: 20°C)
▪
[0‑06]: High outdoor ambient temperature.
25°C~43°C (default: 35°C)
▪
[0‑05]: Desired leaving water temperature
when the outdoor temperature equals or
drops below the low ambient temperature.
Between minimum and maximum leaving
water
temperature
[9‑07]°C~[9‑08]°C
(default: 12°C).
Note:
This value should be higher than [0‑04]
as for low outdoor temperatures less cold
water suffices.
▪
[0‑04]: Desired leaving water temperature
when the outdoor temperature equals or
rises above the high ambient temperature.
Between minimum and maximum leaving
water
temperature
[9‑07]°C~[9‑08]°C
(default: 8°C).
Note:
This value should be lower than [0‑05]
as for high outdoor temperatures colder
water is required.
Pump control: Flow target
The hybrid module is designed to operate with a fixed flow. This means that the
pump is controlled to work at a flow target set by the installer. The installer can set
the flow target for:
▪
heat pump only operation,
▪
hybrid operation,
▪
gas boiler only operation.
#
Code
Description
N/A
[8‑0B]
Target flow rate during heat pump operation.
The default value is set to deliver the nominal
capacity of the heat pump with a ΔT over the
emitter of 5°C. Decrease this value if the room
temperature is constantly higher than the
desired room temperature. Increase this value
if you feel discomfort in heat pump only
operation.
Range: 10~20 l/min
▪
For EHYHBH05: 13 l/min (default)
▪
For EHYHBH/X08: 15 l/min (default)
The default values have been set to optimise
comfort and performance. Take care when
changing them.