10
|
Configuration
Installer reference guide
130
E EHFH03S18D
Daikin Altherma 3 R F
4P596806-1C – 2022.09
#
Code
Description
[7.7.1.2]
[1-06]
[1-07]
[1‑08]
[1-09]
If you selected weather-dependent curve as a
setpoint mode, adjust the curve to your needs.
(a)
Set weather-dependent cooling
:
[1-09]
[1-08]
Ta
Tt
[1-06]
[1-07]
▪
T
t
: Target leaving water temperature (main)
▪
T
a
: Outdoor temperature
(a)
Also see
"10.3 Weather-dependent curve"
133].
Leaving water temperature: Additional zone
#
Code
Description
[A.3.1.2.1]
N/A
Select the setpoint mode of the leaving water
temperature.
LWT setpoint mode
:
▪
0 (
Fixed
): Absolute
▪
1 (
Weather dep.
): Weather-dependent
▪
2
(
Fixed/scheduled
):
Absolute
+
scheduled (only if
Unit
control
method
=
LWT control
)
▪
3 (
WD/scheduled
): Weather-dependent +
scheduled (only if
Unit
control
method
=
LWT control
)
[7.7.2.1]
[0-00]
[0-01]
[0-02]
[0-03]
If you selected weather-dependent curve as a
setpoint mode, adjust the curve to your needs.
(a)
Set weather-dependent heating
:
[0-00]
[0-01]
Ta
Tt
[0-03]
[0-02]
▪
T
t
: Target leaving water temperature
(additional)
▪
T
a
: Outdoor temperature