Electrical installation
Installer reference guide
97
E EHFH03S18D
Daikin Altherma 3 R F
4P596806-1C – 2022.09
9.2 Connections to the outdoor unit
Item
Description
Power supply cable
See
"9.2.2 To connect the electrical wiring to the
97].
Interconnection cable
9.2.1 Specifications of standard wiring components
Component
ERLA03D
▲
V3
▼
Power supply
cable
MCA
(a)
13.0 A
Voltage
220-240 V
Phase
1~
Frequency
50 Hz
Wire size
MUST comply with national wiring
regulation.
3-core cable
Wire size based on the current, but not
less than 2.5 mm
2
Interconnection
cable (indoor ↔
outdoor)
Voltage
220-240 V
Wire size
Only use harmonised wire providing
double insulation and suitable for
applicable voltage.
4-core cable
Minimum 1.5 mm
2
Recommended field fuse
16 A
Earth leakage circuit breaker /
residual current device
MUST comply with national wiring
regulation
(a)
MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of
combination with indoor units for exact values).
9.2.2 To connect the electrical wiring to the outdoor unit
1
Remove the service cover. See
"7.2.2 To open the outdoor unit"
2
Strip insulation (20 mm) from the wires.
a
b
a
Strip wire end to this point
b
An excessive strip length may cause electrical shock or leakage
3
Open the wire clamp.
4
Connect the interconnection cable and power supply as follows: