Code
Description
N/A
[8-01]
Maximum running time for domestic hot water
operation. Domestic hot water heating stops
even when the target domestic hot water
temperature is NOT reached.
▪
When system layout = Room thermostat
control: This preset value is only taken into
account if there is a request for space heating
or cooling. If there is NO request for space
heating/cooling, the tank is heated until the
setpoint has been reached.
▪
When system layout ≠ Room thermostat
control: This preset value is always taken into
account.
Range: 5~95 minutes
N/A
[8-02]
Anti-recycling time.
Minimum time between two cycles for domestic
hot water.
Range: 0~10 hours
Remark:
The minimum time is 0.5 hours even
when the selected value is 0.
[8-02]: Anti-recycling time
t
1
0
1
0
[8-01]
[8-02]
[8-00]
1
Heat pump domestic hot water heating mode (1=active, 0=not active)
2
Hot water request for heat pump (1=request, 0=no request)
t
Time
Disinfection
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by periodically
heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function settings MUST be configured by the installer according to
the applicable legislation.
#
Code
Description
[A.4.4.1]
[2‑01]
Disinfection
▪
0:
No
▪
1:
Yes