11
|
Commissioning
Installer reference guide
169
E EHFH03S18D
Daikin Altherma 3 R F
4P596806-1C – 2022.09
5
Use the and buttons to set the desired pump speed.
Result:
Low
Result:
High
To perform an automatic air purge
Prerequisite:
Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1
Set the user permission level to Installer. See
"To set the user permission level
2
Set the air purge mode: go to [A.7.3.1]
>
Installer settings
>
Commissioning
>
Air purge
>
Type
.
3
Select
Automatic
and press .
4
Go to [A.7.3.4]
>
Installer settings
>
Commissioning
>
Air
purge
>
Start air purge
and press to start the air purge function.
Result:
Air purging will start and the following screen will be shown.
11.4.3 To perform a test run
Prerequisite:
Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1
Set the user permission level to Installer. See
"To set the user permission level
2
Go to [A.7.1]: >
Installer settings
>
Commissioning
>
Test run
.
3
Select a test and press .
Example:
Heating
.
4
Select
OK
and press .
Result:
The test run starts. It stops automatically when done (±30 min). To stop it
manually, press , select
OK
and press .
INFORMATION
If 2 user interfaces are present, you can start a test run from both user interfaces.
▪
The user interface used to start the test run displays a status screen.
▪
The other user interface displays a "busy" screen. You cannot use the user
interface as long as the "busy" screen is shown.
11.4.4 To perform an actuator test run
Perform an actuator test run to confirm the operation of the different actuators.
For example, when you select
Pump
, a test run of the pump will start.
Purpose of the actuator test run is to confirm the operation of the different
actuators (e.g., when you select pump operation, a test run of the pump will start).
Prerequisite:
Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1
Set the user permission level to Installer. See
"To set the user permission level
2
Go to [A.7.4]: >
Installer settings
>
Commissioning
>
Actuator
test run
.
3
Select an actuator and press .
Example:
Pump
.