E EHFH03S18D
Daikin Altherma 3 R F
4P596806-1C – 2022.09
#
Code
Description
[A.6.3.3]
[5-05]
Amp. value
: Only applicable in case of full
time power limitation mode.
0 A~50 A, step 1 A
[A.6.3.4]
[5-09]
kW value
: Only applicable in case of full time
power limitation mode.
0 kW~20 kW, step 0.5 kW
Amp. limits for DI
: Only applicable in case of power limitation mode based
on digital inputs and based on current values.
N/A
[5-05]
Limit DI1
0 A~50 A, step 1 A
N/A
[5-06]
Limit DI2
0 A~50 A, step 1 A
N/A
[5-07]
Limit DI3
0 A~50 A, step 1 A
N/A
[5-08]
Limit DI4
0 A~50 A, step 1 A
kW limits for DI
: Only applicable in case of power limitation mode based on
digital inputs and based on power values.
N/A
[5-09]
Limit DI1
0 kW~20 kW, step 0.5 kW
N/A
[5-0A]
Limit DI2
0 kW~20 kW, step 0.5 kW
N/A
[5-0B]
Limit DI3
0 kW~20 kW, step 0.5 kW
N/A
[5-0C]
Limit DI4
0 kW~20 kW, step 0.5 kW
Average timer
The average timer corrects the influence of ambient temperature variations. The
weather-dependent set point calculation is done on the average outdoor
temperature.
The outdoor temperature is averaged over the selected time period.
#
Code
Description
[A.6.4]
[1-0A]
Outdoor average timer:
▪
0: No averaging
▪
1: 12 hours
▪
2: 24 hours
▪
3: 48 hours
▪
4: 72 hours