3/8
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
└─
Space operation
└─
LWT settings
└──────────────────
Main
A.3.1.1.1
R/W
0: Fixed
1: Weather dep.
2: Fixed / scheduled
3: WD / scheduled
A.3.1.1.2.1
[9-01]
Temperature range
Minimum temp (heating)
R/W
15~37°C, step: 1°C
25°C
A.3.1.1.2.2
[9-00]
Temperature range
Maximum temp (heating)
R/W
37~60°C, step: 1°C
55°C
A.3.1.1.2.3
[9-03]
Temperature range
Minimum temp (cooling)
R/W
5~18°C, step: 1°C
5°C
A.3.1.1.2.4
[9-02]
Temperature range
Maximum temp (cooling)
R/W
18~22°C, step: 1°C
22°C
A.3.1.1.5
[8-05]
R/W
0: No
1: Yes
A.3.1.1.7
[2-0C]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
└──────────────────
Additional
A.3.1.2.1
R/W
0: Fixed
1: Weather dep.
2: Fixed / scheduled
3: WD / scheduled
A.3.1.2.2.1
[9-05]
Temperature range
Minimum temp (heating)
R/W
15~37°C, step: 1°C
25°C
A.3.1.2.2.2
[9-06]
Temperature range
Maximum temp (heating)
R/W
37~60°C, step: 1°C
55°C
A.3.1.2.2.3
[9-07]
Temperature range
Minimum temp (cooling)
R/W
5~18°C, step: 1°C
5°C
A.3.1.2.2.4
[9-08]
Temperature range
Maximum temp (cooling)
R/W
18~22°C, step: 1°C
22°C
└──────────────────
Delta T source
A.3.1.3.1
[1-0B]
R/W
3~10°C, step: 1°C
5°C
A.3.1.3.2
[1-0D]
R/W
3~10°C, step: 1°C
5°C
└─
Room thermostat
A.3.2.1.1
[3-07]
Room temp. range
Minimum temp (heating)
R/W
12~18°C, step: A.3.2.4
12°C
A.3.2.1.2
[3-06]
Room temp. range
Maximum temp (heating)
R/W
18~30°C, step: A.3.2.4
30°C
A.3.2.1.3
[3-09]
Room temp. range
Minimum temp (cooling)
R/W
15~25°C, step: A.3.2.4
15°C
A.3.2.1.4
[3-08]
Room temp. range
Maximum temp (cooling)
R/W
25~35°C, step: A.3.2.4
35°C
A.3.2.2
[2-0A]
R/W
-5~5°C, step: 0,5°C
0°C
A.3.2.4
R/W
0: 1°C
1: 0,5°C
└─
Operation range
A.3.3.1
[4-02]
R/W
14~35°C, step: 1°C
22°C
A.3.3.2
[F-01]
R/W
10~35°C, step: 1°C
20°C
└─
Domestic hot water (DHW)
└─
Type
A.4.1
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
└─
Disinfection
A.4.4.1
[2-01]
R/W
0: No
1: Yes
A.4.4.2
[2-00]
R/W
0: Each day
1: Monday
2: Tuesday
3: Wednesday
4: Thursday
5: Friday
6: Saturday
7: Sunday
A.4.4.3
[2-02]
R/W
0~23 hour, step: 1 hour
1
A.4.4.4
[2-03]
R/W
fixed value
60°C
A.4.4.5
[2-04]
R/W
40~60 min, step: 5 min
40 min
└─
Maximum setpoint
A.4.5
[6-0E]
R/W
40~60°C, step: 1°C
60°C
└─
SP mode
A.4.6
R/W
0: Fixed
1: Weather dep.
└─
Weather dependent curve
A.4.7
[0-0B]
Weather-dependent curve
DHW setpoint for high ambient temp. for DHW
WD curve.
R/W
35~[6-0E]°C, step: 1°C
55°C
A.4.7
[0-0C]
Weather-dependent curve
DHW setpoint for low ambient temp. for DHW
WD curve.
R/W
45~[6-0E]°C, step: 1°C
60°C
A.4.7
[0-0D]
Weather-dependent curve
High ambient temp. for DHW WD curve.
R/W
10~25°C, step: 1°C
15°C
A.4.7
[0-0E]
Weather-dependent curve
Low ambient temp. for DHW WD curve.
R/W
-40~5°C, step: 1°C
-10°C
└─
Heat sources
└─
Backup heater
A.5.1.4
[5-01]
R/W
-15~35°C, step: 1°C
0°C
A.5.1.5
[8-0E]
R/W
-15~-7°C, step: 1°C
-7°C
└─
System operation
└─
Auto restart
A.6.1
[3-00]
R/W
0: No
1: Yes
Modulated LWT
Emitter type
Equilibrium temp.
BUH only ambient temp.
Operation day
Start time
Temperature target
Duration
Room temp. step
Space heating OFF temp
Disinfection
Room temp. offset
Space Cooling ON temp
Delta T cooling
LWT setpoint mode
Delta T heating
LWT setpoint mode
(*1) Only applicable for models where cooling is possible
(*2) EHFH03S18D
▲
3V
▼
4P596814-1B - 2022.09