10
|
Configuration
Installer reference guide
123
E EHFH03S18D
Daikin Altherma 3 R F
4P596806-1C – 2022.09
The other user interface is set to
At unit
.
Space heating/cooling: Number of LWT zones
#
Code
Description
[A.2.1.8]
[7-02]
Number of LWT zones
▪
0 (
1 LWT zone
)
▪
1 (
2 LWT zones
)
The system can supply leaving water to up to 2 water temperature zones. During
configuration, the number of water zones must be set.
1 LWT zone
:
There is only 1 leaving water temperature zone. This zone is called the main leaving
water temperature zone.
a
a
Main LWT zone
2 LWT zones
:
There are 2 leaving water temperature zones:
▪
The zone with the lowest leaving water temperature (in heating) is called the
main leaving water temperature zone.
▪
The zone with the highest leaving water temperature (in heating) is called the
additional leaving water temperature zone.
Remark:
In practice, the main leaving water temperature zone consists of the
higher load heat emitters and a mixing station is installed to achieve the desired
leaving water temperature.
a
b
c
a
Additional LWT zone
b
Main LWT zone
c
Mixing station