10
|
Configuration
Installer reference guide
143
E EHFH03S18D
Daikin Altherma 3 R F
4P596806-1C – 2022.09
[C‑07]=0: leaving water temperature control
Under leaving water temperature control, room frost protection is NOT
guaranteed. However, if [2‑06] is set to "1", limited frost protection by the unit is
possible:
▪
When the leaving water temperature home page is OFF and the outdoor ambient
temperature drops below 4°C, then the unit will supply leaving water to the heat
emitters to heat up the room again, and the leaving water temperature setpoint
will be lowered.
▪
When the leaving water temperature home page is ON, then the unit will supply
leaving water to the heat emitters to heat up the room according to normal logic.
Shut-off valve
The following is only applicable in case of 2 leaving water temperature zones. In
case of 1 leaving water temperature zone, connect the shut-off valve to the
heating/cooling output.
The shut-off valve, which is in the main leaving water temperature zone, output is
configurable.
INFORMATION
During defrost operation, the shut-off valve is ALWAYS opened.
Thermo On/OFF
: the valve closes, depending on [F-0B] when there is no heating
demand from the main zone. Enable this setting to:
▪
avoid leaving water supply to the heat emitters in the main LWT zone (through
the mixing valve station) when there is request from the additional LWT zone.
▪
activate the On/OFF pump of the mixing valve station ONLY when there is
demand. See
29].
#
Code
Description
N/A
[F-0B]
The shut-off valve:
▪
0 (
No
)(default): is NOT influenced by heating or
cooling demand.
▪
1 (
Yes
): closes when there is NO heating or
cooling demand.
INFORMATION
The setting [F‑0B] is only valid when there is a thermostat or external room
thermostat request setting (NOT in case of leaving water temperature setting).
Cooling
: The shut-off valve closes, depending on [F-0C] when the unit is running
in cooling operation mode. Enable this setting to avoid cold leaving water through
the heat emitter and the forming of condensation (e.g. under floor heating loops or
radiators).
#
Code
Description
N/A
[F-0C]
The shut-off valve:
▪
0 (
No
): is NOT influenced by changing the space
operation mode to cooling.
▪
1 (
Yes
)(default): closes when the space
operation mode is cooling.