10
|
Configuration
Installer reference guide
126
E EHFH03S18D
Daikin Altherma 3 R F
4P596806-1C – 2022.09
Domestic hot water: DHW pump
#
Code
Description
[A.2.2.A]
[D-02]
DHW pump
:
▪
0:
No
: NOT installed
▪
1:
Secondary rtrn
: Installed for instant hot
water when water is tapped. The user sets the
operation timing of the domestic hot water
pump using the schedule. Control of this pump
is possible with the user interface.
▪
2:
Disinf. shunt
: Installed for disinfection.
It runs when the disinfection function of the
domestic hot water tank is running. No further
settings are needed.
Thermostats and external sensors
NOTICE
If an external room thermostat is used, the external room thermostat will control the
room frost protection. However, the room frost protection is only possible if the
leaving water temperature control on user interface of the unit is turned ON.
29].
#
Code
Description
[A.2.2.4]
[C-05]
Contact type main
In external room thermostat control, the contact
type of the optional room thermostat or heat
pump convector for the main leaving water
temperature zone must be set. See
▪
1 (
Thermo ON/OFF
): The connected external
room thermostat or heat pump convector
sends the heating or cooling demand by the
same signal as it is connected to only 1 digital
input (preserved for the main leaving water
temperature zone) on the indoor unit (X2M/1).
Select this value in case of a connection to the
heat pump convector (FWXV).
▪
2 (
H/C request
)(default): The connected
external room thermostat sends separate
heating and cooling demand and is therefore
connected to the 2 digital input (preserved for
the main leaving water temperature zone) on
the indoor unit (X2M/1 and 2). Select this value
in case of connection with the wired (EKRTWA)
or wireless (EKRTR1 or EKRTRB) room
thermostat.