EWSAH/X06D
Daikin Altherma 3 WS
4P675764-1 – 2022.04
Setup
M1
B
A
a
b
A
Main leaving water temperature zone
B
One single room
a
Heat pump con controller
b
Remote outdoor sensor
▪
For more information about connecting the electrical wiring to the unit, see
"9.2 Overview of electrical connections for external and internal
actuators"
▪
The heat pump convectors are directly connected to the indoor unit.
▪
A shut-off valve (field supply) is installed before the underfloor heating to
prevent condensation on the floor during cooling operation.
▪
The desired room temperature is set via the controller of the heat pump
convectors. There are different controllers and setups possible for the heat pump
convectors. For more information, see:
-
The installation manual of the heat pump convectors
-
The installation manual of the heat pump convector options
-
The addendum book for optional equipment
▪
The space heating/cooling demand signal is sent to one digital input on the
indoor unit (X2M/35 and X2M/30).
▪
The space operation mode is sent by one digital output (X2M/4 and X2M/3) on
the indoor unit to:
-
The heat pump convectors
-
The shut-off valve
Configuration
Setting
Value
Unit temperature control:
▪
#: [2.9]
▪
Code: [C-07]
1 (
External room thermostat
):
Unit operation is decided by the
external thermostat.
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7-02]
0 (
Single zone
): Main