6
|
Application guidelines
Installer reference guide
53
EWSAH/X06D
Daikin Altherma 3 WS
4P675764-1 – 2022.04
a
b
A
B
1
2
3
4
5
A8P
A
Indoor unit
B
Energy management system
a
Power limitation activation
b
Backup heater
P
i
t
DI4
DI3
DI1
a
b
P
i
Power input
t
Time
DI
Digital inputs (power limitation levels)
a
Power limitation active
b
Actual power input
Setup
▪
Demand PCB (option EKRP1AHTA) needed.
▪
Maximum four digital inputs are used to activate the corresponding power
limitation level:
-
DI1 = strongest limitation (lowest energy consumption)
-
DI4 = weakest limitation (highest energy consumption)
▪
Specification of the digital inputs:
-
DI1: S9S (limit 1)
-
DI2: S8S (limit 2)
-
DI3: S7S (limit 3)
-
DI4: S6S (limit 4)
▪
Refer to the wiring diagram for more information.
Configuration
▪
Set the power consumption control settings in [9.9] via the user interface (for the
description of all settings, see
195]):
-
Select limitation by digital inputs.
-
Select the type of limitation (power in kW or current in A).
-
Set the desired power limitation level corresponding to each digital input.
INFORMATION
In case more than 1 digital input is closed (at the same time), the digital input priority
is fixed: DI4 priority>…>DI1.