12
|
Commissioning
Installer reference guide
210
EWSAH/X06D
Daikin Altherma 3 WS
4P675764-1 – 2022.04
Backup heater circuit breaker
F1B (field supply) is turned ON.
The correct pipe size is installed and the
pipes
are properly insulated.
There is NO
water leak
inside the indoor unit.
The
air purge
valve is open (at least 2 turns).
The
pressure relief valve
purges water when opened. Clean water MUST come out.
The
shut-off valves
are properly installed and fully open.
The
domestic hot water tank
is filled completely.
The
central water loop circuit
and
water circuit
are filled correctly.
NOTICE
When the central water loop circuit is not ready to be used, the system can be set to
Compressor forced off
mode. To do this, set [9.5.2]=1 (
Compressor forced
off
=
enabled
).
Space heating and domestic hot water are then provided by the backup heater.
Cooling is NOT possible when this mode is active. All commissioning related to or
making use of the central water loop circuit should NOT be performed until the
central water loop circuit is filled and
Compressor forced off
is deactivated.
12.4 Checklist during commissioning
To perform an
air purge
on the water circuit.
To perform a
test run
.
To perform an
actuator test run
.
Underfloor screed dryout function
The underfloor screed dryout function is started (if necessary).
12.4.1 Air purge function on the water circuit
When commissioning and installing the unit, it is very important to remove all air in
the water circuit. When the air purge function is running, the pump operates
without actual operation of the unit and the remove of air in the water circuit will
start.
NOTICE
Before starting the air purge, open the safety valve and check if the circuit is
sufficiently filled with water. Only if water escapes the valve after opening it, you can
start the air purge procedure.
There are 2 modes to purge air:
▪
Manually: the unit will operate with a fixed pump speed and in a fixed or custom
position of the 3-way valve. The custom position of the 3-way valve is a helpful
feature to remove all air from the water circuit in space heating or domestic hot
water heating mode. The operation speed of the pump (slow or quick) can also
be set.