11
|
Configuration
Installer reference guide
183
EWSAH/X06D
Daikin Altherma 3 WS
4P675764-1 – 2022.04
t
T
DHW
T
HP ON
T
HP OFF
T
HP MAX
T
U
=
T
BUH OFF
[6-01]
[6-00]
T
U
= 60°C
T
HP MAX
= 50°C
[6-01] = 2°C
[6-00] = 2°C
HP
BUH
HP
5
10
20
30
40
46
48
50
60
BUH
Backup heater
HP
Heat pump. If heating up time by the heat pump takes too long, auxiliary heating by
the backup heater can take place
T
BUH OFF
Backup heater OFF temperature (T
U
)
T
HP MAX
Maximum heat pump temperature at sensor in domestic hot water tank
T
HP OFF
Heat pump OFF temperature (T
HP MAX
−[6-01])
T
HP ON
Heat pump ON temperature (T
HP OFF
−[6-00])
T
DHW
Domestic hot water temperature
T
U
User setpoint temperature (as set on the user interface)
t
Time
Example: setpoint (T
U
)≤maximum heat pump temperature–[6‑01] (T
HP MAX
–[6‑01])
t
[6-00]
HP
5
10
20
30
40
43
45
T
U
=T
HP OFF
T
HP MAX
T
DHW
T
HP ON
50
HP
Heat pump. If heating up time by the heat pump takes too long, auxiliary heating by
the backup heater can take place
T
HP MAX
Maximum heat pump temperature at sensor in domestic hot water tank
T
HP OFF
Heat pump OFF temperature (T
HP MAX
−[6-01])
T
HP ON
Heat pump ON temperature (T
HP OFF
−[6-00])
T
DHW
Domestic hot water temperature
T
U
User setpoint temperature (as set on the user interface)
t
Time
INFORMATION
The maximum heat pump temperature depends on the ambient temperature. For
more information, see the operation range.
WD curve type
There are 2 methods to define the weather-dependent curves:
▪
2-points
(see
▪
Slope-Offset
(see
149])
In [2.E]
WD curve type
, you can choose which method you want to use.
In [5.E]
WD curve type
, the chosen method is shown read-only (same value as in
[2.E]).