11
|
Configuration
Installer reference guide
226
ERLA11~W1 + EBVH16SU23DJ
Daikin Altherma 3 R F
4P655196-1 – 2021.09
#
Code
Description
[9.9.3]
[5-05]
Limit
: Only applicable in case of full time
current limitation mode.
0 A~50 A
Limits when [9.9.1]=
Inputs
and [9.9.2]=
Amp
:
#
Code
Description
[9.9.4]
[5-05]
Limit 1
: 0 A~50 A
[9.9.5]
[5-06]
Limit 2
: 0 A~50 A
[9.9.6]
[5-07]
Limit 3
: 0 A~50 A
[9.9.7]
[5-08]
Limit 4
: 0 A~50 A
Limit when [9.9.1]=
Continuous
and [9.9.2]=
kW
:
#
Code
Description
[9.9.8]
[5-09]
Limit
: Only applicable in case of full time
power limitation mode.
0 kW~20 kW
Limits when [9.9.1]=
Inputs
and [9.9.2]=
kW
:
#
Code
Description
[9.9.9]
[5-09]
Limit 1
: 0 kW~20 kW
[9.9.A]
[5-0A]
Limit 2
: 0 kW~20 kW
[9.9.B]
[5-0B]
Limit 3
: 0 kW~20 kW
[9.9.C]
[5-0C]
Limit 4
: 0 kW~20 kW
Priority heater
This setting defines the priority of the electrical heaters depending on applicable
limitation. As no booster heater is present, the backup heater will always be
prioritised.
#
Code
Description
[9.9.D]
[4-01]
Priority heater
:
▪
0
None
: The backup heater is prioritised.
▪
1
Booster
heater
: After restart, the
setting will be reverted back to 0=
None
and
the backup heater will be prioritised.
▪
2
Backup heater
: The backup heater is
prioritised.
BBR16
See
"6.6.4 BBR16 power limitation"
61] for detailed information about this
functionality.
INFORMATION
Restriction:
BBR16 settings are only visible when the language of the user interface is
set to Swedish.
Содержание Altherma 3 R F
Страница 309: ...13 13 ...
Страница 310: ......
Страница 311: ......
Страница 312: ...4P655196 1 2021 09 Copyright 2021 Daikin Verantwortung für Energie und Umwelt ...