Application guidelines
Installer reference guide
41
ERLA11~W1 + EBVH16SU23DJ
Daikin Altherma 3 R F
4P655196-1 – 2021.09
▪
For more information about connecting the electrical wiring to the unit, see:
-
"9.2 Connections to the outdoor unit"
-
"9.3 Connections to the indoor unit"
▪
For each room, a shut-off valve (field supplied) is installed to avoid leaving water
supply when there is no heating or cooling demand.
▪
A bypass valve must be installed to make water recirculation possible when all
shut-off valves are closed. To guarantee reliable operation, provide a minimum
water flow as described in table "To check the water volume and flow rate" in
104].
▪
The user interface integrated in the indoor unit decides the space operation
mode. Mind that the operation mode on each room thermostat must be set to
match the indoor unit.
▪
The room thermostats are connected to the shut-off valves, but do NOT have to
be connected to the indoor unit. The indoor unit will supply leaving water all the
time, with the possibility to program a leaving water schedule.
Configuration
Setting
Value
Unit temperature control:
▪
#: [2.9]
▪
Code: [C-07]
0 (
Leaving water
): Unit operation is
decided based on the leaving water
temperature.
Number of water temperature zones:
▪
#: [4.4]
▪
Code: [7-02]
0 (
Single zone
): Main
Benefits
Compared with underfloor heating for one room:
▪
Comfort.
You can set the desired room temperature, including schedules, for
each room via the room thermostats.
Radiators – Multiple external room thermostats
Setup
A
B
C
b
a
M1
a
M2
c
230
V AC
230
V AC
A
Main leaving water temperature zone
B
Room 1
C
Room 2
a
External room thermostat
b
Bypass valve
c
Relay