11
|
Configuration
Installer reference guide
236
ERLA11~W1 + EBVH16SU23DJ
Daikin Altherma 3 R F
4P655196-1 – 2021.09
Additional zone pump fixed PWM
The speed of the additional zone pump can be fixed with this setting.
#
Code
Description
[9.P.3]
[7-0A]
Add zone pump fixed PWM
: Fixed pump
speed for additional (direct) zone.
▪
20~95% (default: 95)
Main zone pump fixed PWM
The speed of the main zone pump can be fixed with this setting.
#
Code
Description
[9.P.4]
[7-0B]
Main zone pump fixed PWM
: Fixed pump
speed for main (mixed) zone.
▪
20~95% (default: 95)
Mixing valve turning time
If a third party mixing valve is installed in combination with controller EKMIKPOA,
the valve turning time must be set accordingly.
For this setting, space heating/cooling and tank operation MUST be off:
[C.2]
Space
heating/cooling
=0 (
Off
) and [C.3]
Tank
=0 (
Off
). See
237].
#
Code
Description
[9.P.5]
[7-0C]
Mixing valve turning time
: Time in
seconds for the mixing valve to turn from one
side to the other.
▪
20~300 sec (default: 125)
11.6.10 Commissioning
Overview
The following items are listed in the submenu:
A
Commissioning
User profile
Installer settings
Information
Operation
[A]
Commissioning
[A.1]
Operation test run
[A.2]
Actuator test run
[A.3]
Air purge
[A.4]
UFH screed dryout
About commissioning
11.6.11 User profile
[B]
User profile
"To change the user permission level"
B
User profile
Operation
Commissioning
Installer settings
Malfunctioning
Содержание Altherma 3 R F
Страница 309: ...13 13 ...
Страница 310: ......
Страница 311: ......
Страница 312: ...4P655196 1 2021 09 Copyright 2021 Daikin Verantwortung für Energie und Umwelt ...