11/13
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.I
[9-08]
R/W
18~22°C, step: 1°C
22°C
9.I
[9-09]
R/W
1~18°C, step: 1°C
18°C
9.I
[9-0A]
R/W
[3-07]
~
[3-06]°C, step: 0,5°C
23°C
9.I
[9-0B]
R/W
[3-09]
~
[3-08]°C, step: 0,5°C
23°C
9.I
[9-0C]
R/W
1~6°C, step: 0,5°C
1 °C
9.I
[9-0D]
R/W
0~8, step:1
0: No limitation
1~4: 90~60% pump speed
5~8: 90~60% pump speed during
sampling
6 80% pump speed during sampling
9.I
[9-0E]
6
9.I
[C-00]
R/W
0: Solar priority
1: Heat pump priority
9.I
[C-01]
0
9.I
[C-02]
R/W
0: No
1: Bivalent through header
9.I
[C-03]
R/W
-25~25°C, step: 1°C
0°C
9.I
[C-04]
R/W
2~10°C, step 1°C
3°C
9.I
[C-05]
R/W
0: MMI requests (incl. quick logic)
1: 1 contact
2: 2 contacts
9.I
[C-06]
R/W
0: MMI requests (incl. quick logic)
1: 1 contact
2: 2 contacts
9.I
[C-07]
R/W
0: LWT control
1: Ext RT control
2: RT control
9.I
[C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
9.I
[C-09]
R/W
0: Normally open
1: Normally closed
9.I
[C-0A]
0
9.I
[C-0B]
0
9.I
[C-0C]
0
9.I
[C-0D]
0
9.I
[C-0E]
0
9.I
[D-00]
R/W
0: None
1: BSH only
2: BUH only
3: All heaters
9.I
[D-01]
R/W
0: No
1: Active open
2: Active closed
3: Smart grid
9.I
[D-02]
R/W
0: No DHW pump
1: Instant hot water
2: Disinfection
3: Circulation
4: Circulation and disinfection
9.I
[D-03]
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
9.I
[D-04]
R/W
0: No
1: Pwr consmp ctrl
9.I
[D-05]
R/W
0: Forced off
1: As normal
9.I
[D-07]
R/W (*3)
R/O (*4)
0: No (*4)
1: Solar for DHW (*3)
9.I
[D-08]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
9.I
[D-09]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
6: 100 pulse/kWh (PV meter)
7: 1000 pulse/kWh (PV meter)
8: 1 pulse/m³ (gas meter)
9: 10 pulses/m³ (gas meter)
10: 100 pulses/m³ (gas meter)
9.I
[D-0A]
R/W (*4)
R/O (*3)
0 (*4)
2 (*3)
9.I
[D-0B]
2
9.I
[D-0C]
0
9.I
[D-0D]
0
9.I
[D-0E]
0
9.I
[E-00]
R/O
0~5
0: LT split
9.I
[E-01]
R/O
1
9.I
[E-02]
R/O
0: Reversible (*5)
1: Heating only (*6)
9.I
[E-03]
R/O
3: 6V (*1)
4: 9W (*2)
What is the maximum desired LWT for add. zone in cooling?
What is the allowed undershoot in cooling?
Room temperature hysteresis.
Pump speed limitation
--
Domestic heating water priority.
--
What is the room buffering temperature in heating?
What is the room buffering temperature in Cooling?
Is an external backup heat source connected?
Bivalent activation temperature.
Bivalent hysteresis temperature.
What is the thermo request contact type for the main zone?
What is the thermo request contact type for the add. zone?
What is the unit control method in space operation?
Which type of external sensor is installed?
What is the required alarm output contact type?
--
--
--
--
--
Which heaters are permitted if prefer. kWh rate PS is cut?
Contact type of preferential kWh rate PS installation?
Which type of DHW pump is installed?
Leaving water temperature compensation around 0°C.
Is a demand PCB connected?
Is the pump allowed to run if prefer. kWh rate PS is cut?
Is a solar kit connected?
Is an external kWh meter used for power measurement?
Is an external kWh meter used for power measurement, kWh meter used for smart
grid or a gas meter for hybrid unit?
--
--
--
--
Which type of unit is installed?
Which type of compressor is installed?
What is the indoor unit software type?
What is the number of backup heater steps?
--
(*1) *6V_(*2) *9W_(*3) EBB*_(*4) EBV*_
(*5) *X*_(*6) *H*_(*7) *11*_(*8) *16*_
(*9) *SU*_(*10) *18*_(*11) *23*
4P655201-1 - 2021.09