11
|
Configuration
Installer reference guide
204
ERLA11~W1 + EBVH16SU23DJ
Daikin Altherma 3 R F
4P655196-1 – 2021.09
#
Code
Description
[5.6]
[6-0D]
Heat up mode
:
▪
0:
Reheat only
: Only reheat operation is
allowed.
▪
1:
Schedule + reheat
: The domestic hot
water tank is heated according to a schedule
and between the scheduled heat up cycles,
reheat operation is allowed.
▪
2:
Schedule only
: The domestic hot water
tank can ONLY be heated according to a
schedule.
See the operation manual for more details.
Disinfection
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by periodically
heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function settings MUST be configured by the installer according to
the applicable legislation.
#
Code
Description
[5.7.1]
[2‑01]
Activation
:
▪
0:
No
▪
1:
Yes
[5.7.2]
[2‑00]
Operation day
:
▪
0:
Every day
▪
1:
Monday
▪
2:
Tuesday
▪
3:
Wednesday
▪
4:
Thursday
▪
5:
Friday
▪
6:
Saturday
▪
7:
Sunday
[5.7.3]
[2‑02]
Start time
[5.7.4]
[2‑03]
Tank setpoint
:
60°C
[5.7.5]
[2‑04]
Duration
:
40~60 minutes