11
|
Configuration
Installer reference guide
173
ERLA11~W1 + EBVH16SU23DJ
Daikin Altherma 3 R F
4P655196-1 – 2021.09
0
Malfunctioning
Room
Operation
User profile
Main zone
11.6.2 Room
Overview
The following items are listed in the submenu:
1
Room
Main zone
Malfunctioning
Operation
Additional zone
[1]
Room
Setpoint screen
[1.1]
Schedule
[1.2]
Heating schedule
[1.3]
Cooling schedule
[1.4]
Antifrost
[1.5]
Setpoint range
[1.6]
Room sensor offset
[1.7]
Room sensor offset
[1.9]
Room comfort setpoint
Setpoint screen
Control the room temperature of the main zone via setpoint screen [1]
Room
.
See
156].
Schedule
Indicate if the room temperature is controlled according to a schedule or not.
#
Code
Description
[1.1]
N/A
Schedule
:
▪
No
: Room temperature is directly controlled by
the user.
▪
Yes
: Room temperature is controlled by a
schedule and can be modified by the user.
Heating schedule
Applicable for all models.
Define a heating schedule of the room temperature in [1.2]
Heating schedule
.
See
"11.4.3 Schedule screen: Example"
Cooling schedule
Only applicable for reversible models.
Define a cooling schedule of the room temperature in [1.3]
Cooling schedule
.
See