220
D320 PLC User's Manual
The individual words of the register block define the operating parameters for the functioning of a
given PID loop, as well as providing a workspace for the D320 to perform its calculations. These
parameters are summarized in Table 3 below.
TABLE 3 – PID Parameter Block
Word #
Description
Type
Abbrev.
Range
0
Status Register
System Output
SR
See Table 3
1
Setpoint
User Input
SP
-327.67 – +327.67
2
Process Value
System Input
PV
-327.67 – +327.67
3
Process Value (Scaled)
System Input
PVs
-327.67 – +327.67
4
Control Value
System Output
CV
-327.67 – +327.67
5
Control Value (Scaled)
System Output
CV
-327.67 – +327.67
6
Control Value Maximum
User Input
CVmax
-327.67 – +327.67
7
Control Value Minimum
User Input
CVmin
-327.67 – +327.67
8
Proportional Term
User Input
Kp
0 – +327.67
9
Integral Term
User Input
Ki
0 – +327.67
10
Derivative Term
User Input
Kd
0 – +327.67
11
FeedForward or Bias
User Input
FF/Bias
-327.67 – +327.67
12
Sampling Cycle Time (unit: 10ms)
User Input
Dt
0.01s – +327.67s
13
Dead Band
User Input
DB
-327.67 – +327.67
14
Manual CV Setting
User Input
CVm
-327.67 – +327.67
15
Reserved
-
-
-
16
Reserved
-
-
-
17
Maximum Scaling Value
User Input
Smax
-327.67 – +327.67
18
Minimum Scaling Value
User Input
Smin
-327.67 – +327.67
19
Number of PID Operations
System Output
-
0 – 65535
20-31
Reserved
-
-
-
Содержание D320 PLC
Страница 1: ...D320 PLC User s Manual...
Страница 18: ...6 D320 PLC User s Manual...
Страница 28: ...16 D320 PLC User s Manual...
Страница 34: ...22 D320 PLC User s Manual...
Страница 78: ...66 D320 PLC User s Manual...
Страница 176: ...164 D320 PLC User s Manual...
Страница 210: ...198 D320 PLC User s Manual...
Страница 258: ...246 D320 PLC User s Manual...