180
D320 PLC User's Manual
Periodic Inspection and Preventive Maintenance
The D320 PLC Series requires regular inspection and maintenance for proper operation. The following
items should be checked every six months.
Item
What to Check
Criteria
Test
Equipment
Supplied
Power
Does the voltage measured within the
power terminal fall within the
specified range?
Voltage must fall within the power
module input voltage specifications.
Voltmeter
Does the temperature fall within the
specified range?
0 to 55°C (32 to 131°F)
Thermometer
Does the humidity fall within the
specified range?
Humidity levels below 30% RH.
Hygrometer
Environment
Is there any dust present?
No dust.
Visual
I/O Power
Does the control voltage supplied to
the I/O modules fall within the
specified limit?
Control voltage must fall within the
input and output modules
specifications.
Voltmeter
Are all of the modules secure?
Is the connection cable secure?
Module
Mounting and
Wiring
Is the external wiring screw loose?
All should be firmly secured.
Screwdriver
Contact relay
Electric life: approx. 10K to 300K
operations – refer to output module
specifications.
Life
expectancy of
Parts
Battery
3 years at 25°C (77°F)
Содержание D320 PLC
Страница 1: ...D320 PLC User s Manual...
Страница 18: ...6 D320 PLC User s Manual...
Страница 28: ...16 D320 PLC User s Manual...
Страница 34: ...22 D320 PLC User s Manual...
Страница 78: ...66 D320 PLC User s Manual...
Страница 176: ...164 D320 PLC User s Manual...
Страница 210: ...198 D320 PLC User s Manual...
Страница 258: ...246 D320 PLC User s Manual...