56
D320 PLC User's Manual
F0.0 to F0.15 (F0 word register) System/Diagnostic Functions
Address
Function
Details
Remarks
F0.0
System check
When power is applied, the system runs self-
diagnostics. Should any fault exist, the error lamp is
turned on. Output and operation are halted.
Normal: Off
F0.1
CPU ROM check
When power is applied, the system self-checks the
ROM. Should any faults exist, the error lamp is
turned on. Output and operation are halted.
Normal: Off
F0.2
CPU RAM check
When the power is applied, the system self-checks
the RAM. Should any faults exist, the error lamp is
turned on. Output and operation are halted.
Normal: Off
F0.3
User program memory
error
If the user program memory is damaged or the
program is faulty, the error lamp is turned on.
Output and operation are halted.
Normal: Off
F0.4
Program check
The CPU initially runs and checks the user
program's syntax. In the case of an error, the error
lamp is turned on. Output and operation are halted.
Normal: Off
F0.5
Module range error
Indicates an invalid R address (>127) used.
Normal: Off
F0.6
Module change error
On when an I/O module is removed/added/fails
while the system is running. The error lamp is on
and the CPU keeps running. Turned off when the
error is corrected.
Normal: Off
F0.7
Module type error
On when module information that is stored in the
CPU and module that is installed are different types.
The error lamp is turned on and operation stops.
Normal: Off
F0.8
Input data control
Off when the running CPU input module's data is
not updated. (Input update is turned Off.)
Normal: On
F0.9
Output data control
Off to suspend updating of the output modules while
the CPU is in the run state. (Output update is turned
Off.) The outputs are maintained in their last valid
state prior to update being disabled.
Normal: On
F0.10
All outputs OFF
Turns all outputs off while CPU is in the run state.
(Outputs are disabled.)
Normal: On
F0.11
Constant cycle interrupt
On when constant cycle interrupt instructions are
used. See the INT instruction. The cycle time is
defined by the user.
Normal: Off
F0.12
Watchdog error
On when a scan time exceeds the watchdog set
time.
Normal: Off
F0.13
Disable module type
checking
On when the CPU starts the initial run, and the
program is checked without performing input/output
module type verification.
Normal: Off
F0.14
Program changes during
run
On when error-checking the program while in run
mode. If there are syntax errors, the CPU is
stopped.
Normal: Off
F0.15
Run state control
On when the CPU is in the run state. Off when
stopped or paused.
Normal: On
Содержание D320 PLC
Страница 1: ...D320 PLC User s Manual...
Страница 18: ...6 D320 PLC User s Manual...
Страница 28: ...16 D320 PLC User s Manual...
Страница 34: ...22 D320 PLC User s Manual...
Страница 78: ...66 D320 PLC User s Manual...
Страница 176: ...164 D320 PLC User s Manual...
Страница 210: ...198 D320 PLC User s Manual...
Страница 258: ...246 D320 PLC User s Manual...