D320 PLC User's Manual
Input Module
Symptom
Expected Cause
Troubleshooting
No external input power
Supply power.
Low external input voltage
Make sure full voltage is being
supplied.
No inputs on an input module
will turn On (LEDs are not
illuminated).
Terminal screw is loose/
Defective contact
Tighten screw/
Reconnect the module
Inputs will not turn to On state
(LEDs are illuminated).
Defective input circuit
Replace the input module.
Device connected to input module is
defective.
Replace the input device.
Loose input wiring
Reconnect the input wiring.
External input time is too short.
Adjust the input module.
One or more inputs on an I/O
module will not turn On.
Terminal screw is loose/
Defective contact
Tighten screw/
Reconnect module
One or more inputs on an I/O
module will not turn Off.
Defective input circuit
Replace the input module.
Low external input voltage
Make sure full supply voltage is being
input.
Noise error
Troubleshoot for noise.
Input changes On/Off state
erratically.
Terminal screw is loose/
Defective contact
Tighten screw/
Reconnect module
Input display LED will not
illuminate (input is On in PLC).
LED error
Replace the input module.
Содержание D320 PLC
Страница 1: ...D320 PLC User s Manual...
Страница 18: ...6 D320 PLC User s Manual...
Страница 28: ...16 D320 PLC User s Manual...
Страница 34: ...22 D320 PLC User s Manual...
Страница 78: ...66 D320 PLC User s Manual...
Страница 176: ...164 D320 PLC User s Manual...
Страница 210: ...198 D320 PLC User s Manual...
Страница 258: ...246 D320 PLC User s Manual...