54
D320 PLC User's Manual
I/O Address Designation
Example I/O Addressing Configuration
Slot No
00
01
02
03
04
05
06
07
I/O Points
16
16
32
32
0
16
16
32
Word No
R0
R1
R2, R3
R4, R5
-
R6
R7
R8, R9
Bit No
CPU
Unit
R000.0
R000.1
R000.2
:
R000.15
R001.0
R001.1
R001.2
:
R001.15
R002.0
R002.1
R002.2
:
R003.15
R004.0
R004.1
R004.2
:
R005.15
R006.0
R006.1
R006.2
:
R006.15
R007.0
R007.1
R007.2
:
R007.15
R008.0
R008.1
R008.2
:
R009.15
Note:
I/O Address Designation
•
The CPU assigns addresses in sequential order to the I/O modules on the backplane,
starting at address 0.
•
The CPU automatically determines whether the register data from the modules is of type
input or output.
•
The 16-point I/O modules use one word of register memory. The 32-point I/O modules
require 2 words of register memory. Analog and Intelligent function modules can require
from 1 to 4 words of register memory.
•
The combination I/O module consisting of both inputs and outputs is separated into a one
word input and a one word output. On a 16 point mixed I/O module, the eight input or
output points will use up the lower 8 bits (00 to 07) of their respective words.
•
When a slot is empty, a blank (D320BNK300) module can be installed. When addresses
are automatically assigned by the CPU, no address is assigned to a blank module.
(8-slot backplane)
Содержание D320 PLC
Страница 1: ...D320 PLC User s Manual...
Страница 18: ...6 D320 PLC User s Manual...
Страница 28: ...16 D320 PLC User s Manual...
Страница 34: ...22 D320 PLC User s Manual...
Страница 78: ...66 D320 PLC User s Manual...
Страница 176: ...164 D320 PLC User s Manual...
Страница 210: ...198 D320 PLC User s Manual...
Страница 258: ...246 D320 PLC User s Manual...