![Cray ClusterStor L300 Скачать руководство пользователя страница 118](http://html1.mh-extra.com/html/cray/clusterstor-l300/clusterstor-l300_installation-manual_2680121118.webp)
Figure 77. Cabling SSU ESU SAS 12Gb (SSU + 2)
1
1 2
2
1
1
3
4
5
2
2
1
1 2
2
1
1
3
4
5
2
2
EBOD 0
EBOD 1
EAC 0
EAC 1
SSU+2
ESU 1
EBOD 0
EBOD 1
ESU 2
0
1
2
0
1
2
0
1
2
0
1
2
16.3.9 Cable AMMU Networks
The Lustre Distributed Namespace (DNE) feature. The optional additional MMU hardware adds the additional
MDS/MDT capability to a ClusterStor L300 and L300N file system.
The additional optional MMU is deployed as a single 2U24 enclosure containing:
●
2 x MMU EACs (embedded application controllers)
●
22 x 10K HDDs
●
2 x standard 2U24 power supply/fan modules
Each MMU provides two Lustre metadata servers (MDS), one running on each of the 2 MMU EACs and operating
together as an HA failover pair. Normally, each MDS owns and operates 1 of the 2 MDTs provided by the MMU;
during failover the surviving MDS owns and operates both of the 2 MDTs.
Each MDT is provisioned as a single RAID 10 (5+5) array, using a total of 20 HDDs with the remaining 2 HDDs
configured as global hot spares. A single ClusterStor L300 and L300N file system cluster may have from 0 to 8
MMUs installed.
An MMU includes the following cables and connections when installed in a storage rack (occupying 2U of rack
space):
●
2 x power cable, 1 to each PDU
●
2 x LMN cable to each node = 4 total
●
1 x LDN cable to each node = 2 total
The switch port connections are:
Reference
118
Содержание ClusterStor L300
Страница 1: ...ClusterStor L300 and L300N Field Installation Guide 3 0 0 H 6163...
Страница 33: ...Figure 18 Trip the Circuit Breaker Cable the External Power Connections 33...
Страница 90: ...MGMT0 cscli unmount f testfs Perform the First Run Configuration 90...
Страница 125: ...Figure 85 Base Rack Inverted Power Distribution for PX2 5965X3 V2 ClusterStor L300 and L300N Reference 125...